FOAM DELIVERY SYSTEM SEAL CONFIGURATION: NFPA GUIDELINES

BELOW SEAL APPLICATION
(No Foam Dam Required)
Seal Type Minimum Application Rate Minimum Discharge Time (min) Maximum Spacing Between Discharge (Outlets)
gpm/ft² L/min·m²
Mechanical Shoe Seal 0.5 20.4 10 130 ft (39m) 
Tube seal with more than 6 in (152mm) between top of tube and top of pontoon 0.5 20.4 10 60 ft (18m)
Tube seal with less than 6 in (152mm) between top of tube and top of pontoon 0.5 20.4 10 60 ft (18m)
Tube seal with foam discharge below metal secondary seal* 0.5 20.4 10 60 ft (18m)
* Metal secondary seal is equivalent to a foam dam

ABOVE SEAL APPLICATION
(Foam Dam is Required)
Seal Type Minimum Application Rate Minimum Discharge Time (min) Maximum Spacing Between Discharge Outlets with
gpm/ft² L/min·m² 12 in (305mm) Foam Dam        ft (m) 24 in (610mm) Foam Dam        ft (m)
Mechanical shoe seal 0.3 12.2 20 40 (12.2) 80 (24.4)
Tube seal with metal weather shield 0.3 12.2 20 40 (12.2) 80 (24.4)
Fully or partly combustible secondary seal 0.3 12.2 20 40 (12.2) 80 (24.4)
All metal secondary seal 0.3 12.2 20 40 (12.2) 80 (24.4)
Where the fixed foam discharge outlets are mounted above the top of the tank shell, a foam splashboard is necessary due to the effect of winds.

EMISSION REDUCTION SOLUTIONS
Mesa manufactures a range of "GREEN" products to make storage tanks better neighbors. MORE INFO
above ground storage tanks
MESA DRAINS
Mesa manufactures flexible pipe for aboveground storage tank floating roofs. Designs include Armor-Clad, Resist-All-Clad and Mesaflex. MORE INFO
Aboveground Storage Tanks
45 YEARS OF QUALITY
Since 1967, Mesa has provided quality products for ASTs, refineries , storage tank contractors and maintenance companies. MORE INFO
Mesa celebrates 45 Years!